TeSys Deca IEC contactor, 9 A, 3 P, 5 HP at 480 VAC, reversing, 120 VAC 50/60 Hz coil
SKU: LC2D09G7
Main
Range
TeSys
TeSys Deca
Product name
TeSys D
TeSys Deca
Product or Component Type
Reversing contactor
Device short name
LC2D
Contactor application
Resistive load
Motor control
Utilisation category
AC-1
AC-3
device presentation
Preassembled with reversing power busbar
poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
25 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
Motor power kW
2.2 kW at 220...230 V AC 50 Hz
4 kW at 380...400 V AC 50 Hz
4 kW at 415...440 V AC 50 Hz
5.5 kW at 500 V AC 50 Hz
5.5 kW at 660...690 V AC 50 Hz
motor power HP (UL / CSA)
0.5 hp at 115 V AC 60 Hz for 1 phase motors
1 hp at 230/240 V AC 60 Hz for 1 phase motors
2 hp at 200/208 V AC 60 Hz for 3 phase motors
2 hp at 230/240 V AC 60 Hz for 3 phase motors
5 hp at 460/480 V AC 60 Hz for 3 phase motors
7.5 hp at 575/600 V AC 60 Hz for 3 phase motors
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
120 V AC 50/60 Hz
auxiliary contact composition
1 NO + 1 NC
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Overvoltage category
III
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit
25 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
250 A at 440 V for power circuit conforming to IEC 60947
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
Rated breaking capacity
250 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
30 A 104 °F (40 °C) - 10 min for power circuit
61 A 104 °F (40 °C) - 1 min for power circuit
105 A 104 °F (40 °C) - 10 s for power circuit
210 A 104 °F (40 °C) - 1 s for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating
25 A gG at <= 690 V coordination type 1 for power circuit
20 A gG at <= 690 V coordination type 2 for power circuit
10 A gG for signalling circuit conforming to IEC 60947-5-1
Average impedance
2.5 mOhm - Ith 25 A 50 Hz for power circuit
[Ui] rated insulation voltage
Power circuit 690 V IEC 60947-4-1
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Electrical durability
0.6 Mcycles 25 A AC-1 <= 440 V
2 Mcycles 9 A AC-3 <= 440 V
Power dissipation per pole
0.2 W AC-3
1.56 W AC-1
Front cover
With
Interlocking type
Mechanical
Mounting Support
Plate
Rail
Standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product Certifications
DNV
CSA
CCC
UL
GL
LROS (Lloyds register of shipping)
BV
RINA
GOST
UKCA
Connections - terminals
Power circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
Power circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
Power circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
Power circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
Power circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid
Power circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end
Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid
Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid
Tightening torque
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Power circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals Philips No 2
Control circuit 15.05 lbf.in (1.7 N.m) screw clamp terminals pozidriv No 2
Power circuit 22.1 lbf.in (2.5 N.m) screw clamp terminals pozidriv No 2
Operating time
12...22 ms closing
4...19 ms opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
15 Mcycles
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Complementary
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 50/60 Hz
0.8...1.1 Uc -40…140 °F (-40…60 °C) operational AC 50 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 50/60 Hz
Inrush power in VA
70 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
70 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
7.5 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
7 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
2…3 W 50/60 Hz
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Insulation resistance
> 10 MOhm for signalling circuit
Environment
IP degree of protection
IP20 front face IEC 60529
Climatic withstand
IACS E10
IEC 60947-1 Annex Q category D
Protective treatment
TH IEC 60068-2-30
Pollution degree
3
Ambient air temperature for operation
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz
Vibrations contactor closed4 Gn, 5...300 Hz
Shocks contactor open10 Gn for 11 ms
Shocks contactor closed15 Gn for 11 ms
Height
3.03 in (77 mm)
Width
3.5 in (90 mm)
Depth
3.4 in (86 mm)
Net Weight
1.515 lb(US) (0.687 kg)
Ordering and shipping details
Category
US10I1222354
Discount Schedule
0I12
GTIN
3389110383416
Returnability
Yes
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
3.7 in (9.4 cm)
Package 1 Width
4.5 in (11.4 cm)
Package 1 Length
5.5 in (14.0 cm)
Package 1 Weight
28.4 oz (805.0 g)
Unit Type of Package 2
S02
Number of Units in Package 2
6
Package 2 Height
5.9 in (15.0 cm)
Package 2 Width
11.8 in (30.0 cm)
Package 2 Length
15.7 in (40.0 cm)
Package 2 Weight
11.651 lb(US) (5.285 kg)
Unit Type of Package 3
P06
Number of Units in Package 3
96
Package 3 Height
30.3 in (77.0 cm)
Package 3 Width
31.5 in (80.0 cm)
Package 3 Length
23.6 in (60.0 cm)
Package 3 Weight
205.16 lb(US) (93.06 kg)
Contractual warranty
Warranty
18 months
Enter your zip code to see prices
Delivery of products may differ based on your Zip code

New modern look & feel of all machines
Designed to meet the requirements of industrial and HVAC applications
Easier to install and operate with multi-standard screws