Standard control unit, TeSys Ultra, 8A to 32A class 10, 110 to 220VDC/AC
SKU: LUCA32FU
Main
Range
TeSys
Range of Product
TeSys Ultra
Product name
TeSys Ultra
Device short name
LUCA
Product or Component Type
Standard control unit
Device Application
Motor control
Motor protection
Product Specific Application
Basic protection requirements for motor starters: overload and short-circuit
main function available
Earth fault protection
Protection against phase failure and phase imbalance
Protection against overload and short-circuit
Manual reset
Product compatibility
Power base LUB32
Power base LUB38
Power base LUB320
Power base LUB380
Reversing contactor breaker LU2B32FU
Reversing contactor breaker LU2B38FU
[Ue] rated operational voltage
690 V AC
Network frequency
40...60 Hz
Load type
3-phase motor self-cooled
Utilisation category
AC-43
AC-41
AC-44
Motor power kW
15 kW 400...440 V AC 50/60 Hz
15 kW 500 V AC 50/60 Hz
18.5 kW 690 V AC 50/60 Hz
rated motor current adjustment range
8…32 A
Thermal overload class
Class 10 40…60 Hz -13…158 °F (-25…70 °C) IEC 60947-6-2
Class 10 40…60 Hz -13…158 °F (-25…70 °C) UL 508
Tripping threshold
14.2 x Ir +/- 20 %
Phase failure sensitivity
Yes
[Uc] control circuit voltage
110...240 V AC
110...220 V DC
Complementary
Control circuit voltage limits
88...264 V AC 110...240 V in operation
88...242 V DC 110...220 V in operation
55 V AC 110...240 V drop-out
55 V DC 110...220 V drop-out
Typical current consumption
280 mA 110...240 V AC I maximum while closing with LUB32
280 mA 110...240 V AC I maximum while closing with LUB38
280 mA 110...220 V DC I maximum while closing with LUB32
280 mA 110...220 V DC I maximum while closing with LUB38
25 mA 110...240 V AC I rms sealed with LUB32
25 mA 110...240 V AC I rms sealed with LUB38
25 mA 110...220 V DC I rms sealed with LUB32
25 mA 110...220 V DC I rms sealed with LUB38
Heat dissipation
3 W control circuit with LUB32
3 W control circuit with LUB38
Operating time
35 ms opening with LUB32 control circuit
35 ms opening with LUB38 control circuit
50 ms closing with LUB32 control circuit
50 ms closing with LUB38 control circuit
Standards
EN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
Product Certifications
CE
UL
CSA
CCC
EAC
ASEFA
ATEX
Marine
[Ui] rated insulation voltage
690 V IEC 60947-6-2
600 V UL 60947-4-1
600 V CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-6-2
Safe separation of circuit
400 V SELV between the control and auxiliary circuits IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Fixing mode
Plug-in (front face)
Width
1.8 in (45 mm)
Height
2.6 in (66 mm)
Depth
2.4 in (60 mm)
Net Weight
0.298 lb(US) (0.135 kg)
Compatibility code
LUCA
Environment
IP degree of protection
IP20 front panel and wired terminals IEC 60947-1
IP20 other faces IEC 60947-1
IP40 front panel outside connection zone IEC 60947-1
Protective treatment
TH IEC 60068
Ambient air temperature for operation
-13…158 °F (-25…70 °C)
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Operating altitude
6561.68 ft (2000 m)
Fire resistance
1760 °F (960 °C) parts supporting live components IEC 60695-2-12
1202 °F (650 °C) IEC 60695-2-12
Shock resistance
10 gn power poles open IEC 60068-2-27
15 gn power poles closed IEC 60068-2-27
Vibration resistance
2 gn 5…300 Hz power poles open IEC 60068-2-6
4 gn 5…300 Hz power poles closed IEC 60068-2-6
Resistance to electrostatic discharge
8 kV 3 in open air IEC 61000-4-2
8 kV 4 on contact IEC 61000-4-2
Non-dissipating shock wave
1 kV serial mode IEC 60947-6-2
2 kV common mode IEC 60947-6-2
Resistance to radiated fields
9.1 V/m (10 V/m) 3 IEC 61000-4-3
Resistance to fast transients
2 kV 3 serial link IEC 61000-4-4
4 kV 4 all circuits except for serial link IEC 61000-4-4
Immunity to radioelectric fields
10 V IEC 61000-4-6
Immunity to microbreaks
3 ms
Immunity to voltage dips
70 % / 500 ms IEC 61000-4-11
Ordering and shipping details
Category
US10I1122397
Discount Schedule
0I11
GTIN
3389110364057
Returnability
Yes
Country of origin
FR
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.09 in (5.3 cm)
Package 1 Width
3.1 in (8.0 cm)
Package 1 Length
4.06 in (10.3 cm)
Package 1 Weight
4.4 oz (125.0 g)
Unit Type of Package 2
S02
Number of Units in Package 2
23
Package 2 Height
5.9 in (15.0 cm)
Package 2 Width
11.8 in (30.0 cm)
Package 2 Length
15.7 in (40.0 cm)
Package 2 Weight
7.086 lb(US) (3.214 kg)
Contractual warranty
Warranty
18 months
Enter your zip code to see prices
Delivery of products may differ based on your Zip code

Protection against overload and short-circuit
Control unit includes electronic components and the current adjustment dial
Modular, plug & play structure helps you to perform quick maintenance