IEC contactor, TeSys Deca, nonreversing, 50A, 40HP at 480VAC, up to 100kA SCCR, 3 phase, 3 NO, 120VAC 50/60Hz coil, open
SKU: LC1D50AG7
Main
Range
TeSys
TeSys Deca
Range of Product
TeSys Deca
Product or Component Type
Contactor
Device short name
LC1D
Contactor application
Resistive load
Motor control
Utilisation category
AC-4
AC-1
AC-3
AC-3e
poles description
3P
[Ue] rated operational voltage
Power circuit <= 690 V AC 25...400 Hz
Power circuit <= 300 V DC
[Ie] rated operational current
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit
80 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
50 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage
120 V AC 60 Hz
Complementary
Motor power kW
15 kW at 220...230 V AC 50/60 Hz (AC-3)
22 kW at 380...400 V AC 50/60 Hz (AC-3)
30 kW at 500 V AC 50/60 Hz (AC-3)
33 kW at 660...690 V AC 50/60 Hz (AC-3)
25 kW at 415 V AC 50/60 Hz (AC-3)
30 kW at 440 V AC 50/60 Hz (AC-3)
11 kW at 400 V AC 50/60 Hz (AC-4)
15 kW at 220...230 V AC 50/60 Hz (AC-3e)
22 kW at 380...400 V AC 50/60 Hz (AC-3e)
30 kW at 500 V AC 50/60 Hz (AC-3e)
33 kW at 660...690 V AC 50/60 Hz (AC-3e)
25 kW at 415 V AC 50/60 Hz (AC-3e)
30 kW at 440 V AC 50/60 Hz (AC-3e)
Maximum Horse Power Rating
3 hp at 115 V AC 50/60 Hz for 1 phase motors
7.5 hp at 230/240 V AC 50/60 Hz for 1 phase motors
15 hp at 200/208 V AC 50/60 Hz for 3 phase motors
15 hp at 230/240 V AC 50/60 Hz for 3 phase motors
40 hp at 460/480 V AC 50/60 Hz for 3 phase motors
40 hp at 575/600 V AC 50/60 Hz for 3 phase motors
Compatibility code
LC1D
Pole contact composition
3 NO
Protective cover
With
[Ith] conventional free air thermal current
10 A (at 140 °F (60 °C)) for signalling circuit
80 A (at 140 °F (60 °C)) for power circuit
Irms rated making capacity
140 A AC for signalling circuit conforming to IEC 60947-5-1
250 A DC for signalling circuit conforming to IEC 60947-5-1
900 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity
900 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current
400 A 104 °F (40 °C) - 10 s for power circuit
810 A 104 °F (40 °C) - 1 s for power circuit
84 A 104 °F (40 °C) - 10 min for power circuit
208 A 104 °F (40 °C) - 1 min for power circuit
100 A - 1 s for signalling circuit
120 A - 500 ms for signalling circuit
140 A - 100 ms for signalling circuit
Associated fuse rating
10 A gG for signalling circuit conforming to IEC 60947-5-1
100 A gG at <= 690 V coordination type 1 for power circuit
100 A gG at <= 690 V coordination type 2 for power circuit
Average impedance
1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole
3.7 W AC-3
9.6 W AC-1
3.7 W AC-3e
[Ui] rated insulation voltage
Power circuit 600 V CSA
Power circuit 600 V UL
Signalling circuit 690 V IEC 60947-1
Signalling circuit 600 V CSA
Signalling circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Overvoltage category
III
Pollution degree
3
[Uimp] rated impulse withstand voltage
6 kV IEC 60947
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
6 Mcycles
Electrical durability
1.45 Mcycles 50 A AC-3 <= 440 V
1.1 Mcycles 80 A AC-1 <= 440 V
1.45 Mcycles 50 A AC-3e <= 440 V
Control circuit type
AC 60 Hz
Coil technology
Without built-in suppressor module
Control circuit voltage limits
0.3...0.6 Uc -40…158 °F (-40…70 °C) drop-out AC 60 Hz
0.85...1.1 Uc -40…140 °F (-40…60 °C) operational AC 60 Hz
1...1.1 Uc 140…158 °F (60…70 °C) operational AC 60 Hz
Inrush power in VA
140 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C))
Hold-in power consumption in VA
13 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C))
Heat dissipation
4…5 W at 60 Hz
Operating time
4...19 ms opening
12...26 ms closing
Maximum operating rate
3600 cyc/h 140 °F (60 °C)
Connections - terminals
Control circuit: screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible without cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: flexible with cable end
Control circuit: screw clamp terminals 1 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Control circuit: screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) - cable stiffness: solid without cable end
Power circuit: screw connection 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible without cable end
Power circuit: screw connection 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible without cable end
Power circuit: screw connection 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: flexible with cable end
Power circuit: screw connection 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: flexible with cable end
Power circuit: screw connection 1 0.002…0.05 in² (1…35 mm²) - cable stiffness: solid without cable end
Power circuit: screw connection 2 0.002…0.04 in² (1…25 mm²) - cable stiffness: solid without cable end
Tightening torque
Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors flat Ø 6 mm
Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors Philips No 2
Power circuit 70.8 lbf.in (8 N.m) EverLink BTR screw connectors 0.04…0.05 in² (25…35 mm²) hexagonal 0.2 in (4 mm)
Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors 0.002…0.04 in² (1…25 mm²) hexagonal 0.2 in (4 mm)
Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors pozidriv No 2
Power circuit 22.1 lbf.in (2.5 N.m) EverLink BTR screw connectors pozidriv No 2
auxiliary contact composition
1 NO + 1 NC
Auxiliary contacts type
Mechanically linked 1 NO + 1 NC IEC 60947-5-1
Mirror contact 1 NC IEC 60947-4-1
Signalling circuit frequency
25...400 Hz
Minimum switching voltage
17 V for signalling circuit
Minimum switching current
5 mA for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Non-overlap time
1.5 ms on de-energisation between NC and NO contact
1.5 ms on energisation between NC and NO contact
Mounting Support
Rail
Plate
Environment
Standards
CSA C22.2 No 14
EN 60947-4-1
EN 60947-5-1
IEC 60947-4-1
IEC 60947-5-1
UL 508
IEC 60335-1
Product Certifications
DNV
GOST
UL
LROS (Lloyds register of shipping)
GL
RINA
BV
CSA
CCC
IP degree of protection
IP20 front face IEC 60529
Protective treatment
THIEC 60068-2-30
Climatic withstand
IACS E10 exposure to damp heat
IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device
-40…140 °F (-40…60 °C)
140…158 °F (60…70 °C) with derating
Operating altitude
0...9842.52 ft (0...3000 m)
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
V1 conforming to UL 94
Mechanical robustness
Vibrations contactor open 2 Gn, 5...300 Hz)
Vibrations contactor closed 4 Gn, 5...300 Hz)
Shocks contactor closed 15 Gn for 11 ms)
Shocks contactor open 10 Gn for 11 ms)
Height
4.8 in (122 mm)
Width
2.2 in (55 mm)
Depth
4.7 in (120 mm)
Net Weight
1.885 lb(US) (0.855 kg)
Ordering and shipping details
Category
US10I1222357
Discount Schedule
0I12
GTIN
3389119408677
Returnability
Yes
Country of origin
ID
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
2.4 in (6.2 cm)
Package 1 Width
5.3 in (13.5 cm)
Package 1 Length
6.02 in (15.3 cm)
Package 1 Weight
32.5 oz (920.0 g)
Unit Type of Package 2
S02
Number of Units in Package 2
10
Package 2 Height
5.9 in (15.0 cm)
Package 2 Width
11.8 in (30.0 cm)
Package 2 Length
15.7 in (40.0 cm)
Package 2 Weight
21.927 lb(US) (9.946 kg)
Contractual warranty
Warranty
18 months
Enter your zip code to see prices
Delivery of products may differ based on your Zip code

New modern look & feel of all machines
Designed to meet the requirements of industrial and HVAC applications